3 Phase Single Phase High Frequency Online Tower/Rack UPS 10kVA 20kVA 30kVA 40kVA 50kVA
Basic Info
Model NO. | rack 10-50k |
Standby UPS | Sine Wave Output UPS |
Output Capacity | Small Type |
Equipment Mode | Centralized Model |
Brand | OEM |
Nominal Voltage | 220/230/240VAC |
Operating Voltage Range | 110~300VAC |
Power Factor | 0.9 |
Crest Factor | 3:1 |
Efficiency | 95% |
Transport Package | Carton |
Specification | 3000va |
Trademark | oem |
Origin | China |
HS Code | 8504402000 |
Product Description
YDC3300-RT (10-50kVA)
10-50kVA
single phase 3 phase online ups rackmount ups 10kva 15kva 20kva
Building on the best-in-class reliability of the KSTAR UPS platform, the YDC3300-RT rack-mounted UPS provides a dependable and cost-effective power backup solution with a higher power density, a smaller footprint that makes it the ideal solution for distributed IT and edge computing environments.
General Features
Double conversion online design
Input power factor correction (PFC) technology
input power factor up to 0.99
Digital control process (DSP) makes the system more stable and reliable
Parallel redundance function, max six in parallel
LSB synchronization (40~50KVA).
Battery pack can be common connection in parallel operation
30~50 pcs battery are settable
Intelligent charging management
LED+LCD display
Self-diagnosis function
EPO function
Technical Specification
MODEL | YDC3310-RT | YDC3315-RT | YDC3320-RT | YDC3330-RT | YDC3340-RT | YDC3350-RT | ||||||||
Capacity (VA/Watts) | 10k/10k | 15k/15k | 20k/20k | 30k/30k | 40k/40k | 50k/50k | ||||||||
INPUT | ||||||||||||||
Input&Output System | 3/3,3/1,1/1 , Support Double sources input | 3/3, Support Double sources input | ||||||||||||
Nominal Voltage | 380/400/415 (3Ph+N+PE) ; 220/230/240 (P-N) | 380/400/415 (3Ph+N+PE) | ||||||||||||
Operating voltage range | 208~485 | 138~485 | ||||||||||||
Operating frequency range | 40~70Hz | |||||||||||||
Power Factor | ≥0.99 | |||||||||||||
Harmonic distortion (THDi) | ≤3% (100% linear load) | |||||||||||||
Bypass input | ||||||||||||||
Normal voltage (Vac) | 3/3,3/1,1/1 , Support Double sources input | 3/3, Support Double sources input | ||||||||||||
Bypass voltage range | Max. voltage:220V: +25%(optional +10%,+15%,+20% ) ; 230V: +20%(optional +10%,+15% ) ; 240V: +15%(optional +10%) Min. voltage: -45% (optional -10%,-20%,-30%) | |||||||||||||
Bypass Frequency range | Frequency protection range: ±10% | |||||||||||||
Generator input | Support | |||||||||||||
OUTPUT | ||||||||||||||
Output Voltage | 380/400/415Vac,(3Ph+N+PE) 220/230/240Vac,(P-N) | 380/400/415Vac (3Ph+N+PE) | ||||||||||||
Power Factor | 1.0 | |||||||||||||
Output frequency(Hz) | Line mode:Synchronize with input ;when input frequency >±10%%(±1%,±2%,±4%,±5% Optional, Output frequency 50×(1±0.1%)Hz Battery mode :(50/60±0.1%)Hz | |||||||||||||
Waveform | Pure sine wave | |||||||||||||
Crest factor | 3:1 | |||||||||||||
Harmonic distortion(THDV) | ≤2%(100% linear load); ≤4% (100% non linear load) | |||||||||||||
Transfer Time(ms) | 0 Ms | |||||||||||||
Efficiency | UP to 95 | UP to 96 | ||||||||||||
Overload | ≤110% overload for 60 min; 125% overload for 10 min; ≤150% overload for 1 min | |||||||||||||
Bypass Mode | 135% overload for long term; >1000% overload for 100 ms | 135% overload for long term; >1000% overload for 100 ms | ||||||||||||
BATTERY | ||||||||||||||
Battery Voltage | For optional : Optional Voltage: ±180/192/204/216/228/ 240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/ 46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 30 pcs default, 36~50 pcs fully output ; 32~34 pcs Out put power factor 0.9; 30 pcs output power factor 0.8;) | For optional : Optional Voltage: ±180/192/204/216/228/240 /252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/ 50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs fully output ; 32~34 pcs Out put power factor 0.9; 30 pcs output power factor 0.8;) | ||||||||||||
Max charger current (A) | 18 | 20 | 18 | 20 | ||||||||||
Others | ||||||||||||||
Alarm function | Overload,utility abnormal,UPS fail,battery low voltage etc | |||||||||||||
Protection function | Short circuit,overload,overheat,battery low,output low voltage,fan fault,Anti-thunder | |||||||||||||
SYSTEM FEATURES | ||||||||||||||
Overload | Line Mode | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150% turn to bypass mode immediately | ||||||||||||
Bat. Mode | Load≤110%: last 10min, ≤125%: last 1min, ≤150%: last 5S, ≥150% shut down UPS immediately | |||||||||||||
Bypass Mode | Breaker( Load < 125%, long-term operation) | |||||||||||||
Short circuit | Hold whole system | |||||||||||||
Communication interface | RS232, RS485, Parallel, Intelligent Slot(SNMP card/ Relay card(optional)), BMS (optional),EPO port, Output port, MAINTAIN-AUXSWS | |||||||||||||
PHYSICAL | ||||||||||||||
Dimension W×H×D (mm) | 443x131(3U)x580 mm | 440x670x130(3U) | 440x800x175( 4U) | |||||||||||
Net Weight (kg) | 29 | 31 | 32 | 27 | 48 | 51 | ||||||||
ENVIRONMENT | ||||||||||||||
Operating temperature | 0~40ºC | |||||||||||||
Storage temperature | -25ºC~60ºC | |||||||||||||
Humidity range | 0~95% (non-condensing) | |||||||||||||
Altitude | <1500m(when excess 1500m, according to GB/T 3859.2 to derating) | |||||||||||||
Noise Level | <55db | <58 | <62 | <65 | ||||||||||
STANDARDS | ||||||||||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |