Basic Info
Model NO. | YSDU40-24 |
Service | OEM / ODM |
Rated Current | 40A |
Battery Type | Lead-Acid Battery |
Transport Package | 1PC/PE Bag+White Box |
Trademark | Yingjiao |
Origin | Zhejiang, China |
Production Capacity | 150000 Piece/Pieces Per Month |
Product Description
China Din Rail Mounting UPS Power Supply 24V 40A Power Supply Uninterruptible Module for Lead Acid Batteries
Model No. | YSDU40-24 |
DC VOLTAGE RANGE | 21-29 Vdc |
DISCHARGE CURRENT RANGE | 0~40A |
CHARGING CURRENT | 2A |
NORMAL INPUT VOLTAGE | 24Vdc |
INPUT VOLTAGE RANGE | 24~29Vdc |
RATED CURRENT | 40A |
NORMAL BATTERY VOLTAGE | 24Vdc ( 2 x 12Vdc in series or 1 x 24Vdc) |
BATTERY TYPE | Lead-acid battery |
EXTERNAL BATTERY CAPACITIES | 4AH ~ 135AH |
DC BUS OK | Relay contact : Short when DC voltage between 21~29V(±2%), relay contacts |
LED(Green) : DC BUS OK : light ; DC BUS fail : dark | |
BATTERY FAIL | Short when battery voltage falls below 22V(±2%) or battery failure is observed through the battery test function, relay contacts |
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery OK : dark | |
BATTERY DISCHARGE | Relay contact : Short when battery in discharge condition, relay contacts |
LED(Yellow) : light : Battery discharging ; dark : Battery is not discharging or discharging current < 1.0A | |
Working Temperature | -30 ~ +70ºC (Refer to "Derating Curve") |
Withstand Voltage | IP/OP - Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ; Relay - Chassis : 0.5KVac; |
Protection | Short circuit/Battery reverse polarity/Over discharge current /Battery deep discharge |
Connection | I/P :4 poles terminal Block O/P: 6 poles terminal Block |